Module-specific data
|
Number of inputs
|
4
|
Number of outputs
|
4
|
Cable length, shielded
|
200 m
|
With wire-break monitoring in range 0 V to 10 V
|
30 m
|
Voltages, currents, potentials
|
Rated load voltage
|
24 V DC
|
Polarity reversal protection
|
yes
|
Galvanic isolation
|
yes
|
Permissible potential difference
|
|
• between inputs (UCM)
|
3 V
|
• between input (M terminal) and central grounding point
|
75 V DC
|
• Insulation
|
tested at 500 V DC
|
Current consumption
|
|
• from S7-300 backplane bus, max.
|
75 mA
|
• from L+, max.
|
150 mA
|
Power losses, max.
|
3.6 W
|
Status, interrupts, diagnostics
|
Interrupts
|
|
• Limit value interrupt
|
no
|
• Cycle end interrupt
|
yes, parameterizable
|
• Diagnostics interrupt
|
yes, parameterizable
|
Diagnostic functions
|
|
• Fault display for grouped fault
|
yes, red LED
|
• Diagnostic information can be read out
|
yes
|
Analog value generation for inputs
|
Measuring principle
|
successive approximation
|
Conversion time per channel
|
200 μs
|
• Basic conversion time for 4 channels, max.
|
1 ms
|
Resolution
|
|
• Bipolar
|
13 bits + sign
|
• Unipolar
|
14 bits
|
Analog inputs
|
Interference between inputs
|
|
• at 50 Hz
|
65 dB
|
• at 60 Hz
|
65 dB
|
Operational limits (over entire temperature range, referred to input range)
|
|
• with voltage measurement
|
± 0.15 % (with 14-bit resolution)
|
• with current measurement
|
0.25 %
|
Basic error limit (operational limits at 25 °C, referred to input range)
|
0.13 % (with 14-bit resolution)
|
Temperature error (referred to input range)
|
± 0.1 % (with 14-bit resolution)
|
Linearity error (referred to input range)
|
± 0.015 %
|
Repeatability (under steady-state conditions, at 25 °C, referred to input range)
|
± 0.05 %
|
Encoder selection data
|
Input range (rated values)/input resistance
|
|
• Voltage
|
± 1 V; ± 10 V; ± 2.5 V; 0 V to 2 V; 0 V to 10 V: 10 MΩ
|
• Current
|
± 10 mA; 0 mA to 20 mA; 4 mA to 20 mA: 100 Ω
|
Permissible input voltage for voltage input (destruction limit)
|
± 30 V
|
Permissible input current for current input (destruction limit)
|
25 mA
|
Connection of signal encoder
|
|
• for voltage measurement
|
possible
|
• for current measurement
|
|
- as 2-wire transducer
|
not possible
|
- as 4-wire transducer
|
possible
|
• for resistance measurement
|
not possible
|
Output for supplying the transducer (short-circuit proof)
|
10 V/25 mA
|
Data for encoder supply output
|
Rated voltage
|
10 V
|
Output current, max.
|
25 mA
|
Short-circuit proof
|
yes
|
Operating limits (over entire temperature range)
|
0.2 %
|
Temperature error
|
0.002 %/K
|
Basic error for rated voltage
|
0.1 %
|
Outputs
|
Resolution(including overcontrol range)
|
|
• ± 10 V
|
11 bits + sign
|
• from 0 V to 10 V
|
12 bits
|
Conversion time per channel, max.
|
800 μs
|
Settling time
|
|
• for resistive load
|
< 0.1 ms
|
• for capacitive load
|
< 3.3 ms
|
• for inductive load
|
< 0.5 ms
|
Interference between outputs
|
40 dB
|
Substitute values can be switched in
|
yes
|
Operational limits (over entire temperature range, referred to output range)
|
0.5 %
|
Basic error limit (operational limits at 25 °C, referred to output range)
|
0.2 %
|
Linearity error (referred to output range)
|
± 0.05 %
|
Repeatability (under steady-state conditions, at 25 °C, referred to output range)
|
± 0.05 %
|
Output ripple (referred to output range)
|
± 0.05 %
|
Actuator selection data
|
Input ranges (rated values)
|
± 10 V and 0 V to 10 V (switchover)
|
Load impedance
|
|
• for voltage outputs, min.
|
3 kΩ
|
• for capacitive load, max.
|
1 μF
|
• for inductive load, max.
|
1 mH
|
Voltage output
|
|
• Short-circuit proof
|
yes
|
• Short-circuit current, max.
|
8 mA
|
Connection of the actuators for voltage output
|
|
• as 2-wire connection
|
possible
|
• as 4-wire connection
|
not possible
|
Dimensions and weight
|
Dimensions (w x h x d)
|
40 mm x 125 mm x 120 mm
|
Weight, approx.
|
300 g
|