详细说明 |
|
|
品牌:MARSH BELLORFAM | 产地: | 价格:1人民币/个 | 规格: | 简要说明: | | | | 详细介绍:
|
上海冠佑电气自动化有限公司随时欢迎您的来电咨询,低价现货供应 。
电话:021-60483978 13916770581
传真:021-34689102 联系人:陈尉
商务QQ:1305857511 邮箱:2265736@163.com
网址:www.gyautomation.com
MARSH BELLORFAM(马士贝罗浮) 电气转换器 一级代理 |
|
Type 1000 |
|
Type 1000 I/P & E/P Transducers |
- Low Cost
- Built-in Volume Booster
- Small Size
- Field Reversible
- Low Air consumption
- Mounts at Any Angle
- Convenient External Span & Zero Adjusts
(Except for Explosion Proof Models)
- Light Weight
- Wide Supply Pressure Range
- Low Supply Pressure Sensitivity
|
|
Product Detail: |
The Type 1000 Transducer is an electro-pneumatic device that reduces a supply pressure to a regulated output pressure directly proportional to an electrical input signal. The Type 1000 accepts a wide range of supply pressures, ranging from a minimum of 3 psig (0.2 BAR) above the maximum output up to 100 psig (6.9 BAR). An integral pneumatic volume booster is included in the design to provide high flow capacity (up to 12 SCFM/339 slpm). Model selections include general purpose, NEMA 4X Type, extended range, high relief, intrinsically safe, and explosion proof. |
Part Numbers: |
T-1000 General Purpose ordering information: |
Input |
Output* |
Part Number |
Impedance (nominal) |
psig |
BAR |
4-20mA |
3-9 |
0.2-0.6 |
961-072-000 |
90Ω |
9-15 |
0.6-1.0 |
961-073-000 |
90Ω |
3-15 |
0.2-1.0 |
961-070-000 |
180Ω |
3-27 |
0.2-1.9 |
961-074-000 |
220Ω |
6-30 |
0.4-2.1 |
961-075-000 |
220Ω |
1-17 |
0.07-1.2 |
961-116-000 |
250Ω |
3-15 |
0.2-1.0 |
961-089-000 |
180Ω |
10-50mA |
3-15 |
0.2-1.0 |
961-076-000 |
70Ω |
3-27 |
0.2-1.9 |
961-077-000 |
85Ω |
6-30 |
0.4-2.1 |
961-078-000 |
85Ω
============
|
0-5V |
3-15 |
0.2-1.0 |
961-079-000 |
615Ω |
3-27 |
0.2-1.9 |
961-080-000 |
530Ω |
6-30 |
0.4-2.1 |
961-081-000 |
530Ω |
1-9V |
3-15 |
0.2-1.0 |
961-085-000 |
985Ω |
3-27 |
0.2-1.9 |
961-086-000 |
840Ω |
6-30 |
0.4-2.1 |
961-087-000 |
840Ω |
NOTE: For NEMA4X, add 004 suffix. |
T-1000 extended range ordering information: |
Input |
Output* |
Part Number |
Impedance (nominal) |
psig |
BAR |
0-60mA |
2-120 |
0.1-8.3 |
961-107-000 |
220Ω |
4-20mA |
3-120 |
0.2-8.3 |
961-111-000 |
260Ω |
2-60 |
0.1-4.1 |
961-117-000 |
225Ω |
0-10V |
3-120 |
0.2-8.3 |
961-112-000 |
805Ω |
0-5V |
2-60 |
0.1-4.1 |
961-118-000 |
500Ω |
T-1000 HIGH RELIEF ordering information: |
Input |
Output* |
Part Number |
Impedance (nominal) |
psig |
BAR |
4-20mA |
3-9 |
0.2-0.6 |
961-130-000 |
90Ω |
9-15 |
0.6-1.0 |
961-131-000 |
90Ω |
3-15 |
0.2-1.0 |
961-132-000 |
180Ω |
3-27 |
0.2-1.9 |
961-133-000 |
220Ω |
6-30 |
0.4-2.1 |
961-134-000 |
220Ω |
3-15 |
0.2-1.0 |
961-135-000 |
180Ω |
1-17 |
0.07-1.2 |
961-136-000 |
250Ω |
10-50mA |
3-15 |
0.2-1.0 |
961-137-000 |
70Ω |
3-27 |
0.2-1.9 |
961-138-000 |
85Ω |
6-30 |
0.4-2.1 |
961-139-000 |
85Ω |
* For output pressures less than 3 psi (0.2 BAR) or greater than 30 psi (21 BAR), the Type 1000 transducer can be coupled to Bellofram Type 75 pneumatic relay. Consult Applications Engineers for further information. ** NEMA 4 type enclosure option available on all input/output ranges. This option is separate from explosion proof, NEMA 4 units. |
Type 1000 Explosion Proof |
Input |
Output* |
Part Number |
Impedance (nominal) |
Agency Approvals (see notes) |
psig |
BAR |
4-20mA |
3-15 |
0.2-1.0 |
961-098-000 |
180Ω |
Explosion-Proof, Factory Mutual1 |
3-15 |
0.2-1.0 |
961-098-100 |
180Ω |
CSA Explosion Proof |
1-9v |
3-15 |
20-100 |
961-142-000 |
985Ω |
Explosion Proof Factory Mutual1 |
Type 1000 Intrinsically Safe |
4-20mA |
3-15 |
0.2-1.0 |
961-099-000 |
180Ω |
Intrinsically Safe, Factory Mutual3,4 |
3-27 |
0.2-1.9 |
961-100-000 |
220Ω |
Intrinsically Safe, Factory Mutual3,4 |
3-15 |
0.2-1.0 |
961-105-000 |
180Ω |
Intrinsically Safe, CSA5 |
3-27 |
0.2-1.9 |
961-106-000 |
220Ω |
Intrinsically Safe, CSA5 |
6-30 |
0.4-2.1 |
961-101-000 |
220Ω |
Intrinsically Safe, Factory Mutual3,4 |
15-3 |
1.0-0.2 |
961-175-000 |
180Ω |
Intrinsically Safe, Factory Mutual3,4 |
27-3 |
1.9-0.2 |
961-176-000 |
220Ω |
Intrinsically Safe, Factory Mutual3,4 |
30-6 |
2.1-0.4 |
961-177-000 |
220Ω |
Intrinsically Safe, Factory Mutual3,4 |
*For output pressures less than 3 psi or greater than 30 psi the Type 1000 transducer can be coupled to Bellofram Type 75 pneumatic relay. Consult application engineers for further information. |
Agency Approval Notes:
- The Type 1000 Explosion-Proof Transducer has been submitted, tested and approved by Factory Mutual Research for use in hazardous locations for Class I, Division 1, Group D, Class II, Division 1, Groups E, F & G and Class III requirements. It also has been approved to meet NEMA 4 Outdoor requirements.
- Canadian Standards Association certified for hazardous locations: Class I, Group D, Class II, Groups E, F and G, Class III, CSA Enc. 4.
- Factory Mutual Research Approved as intrinsically Safe for Class I, II, III, Division 1, Groups A, B, C, D, E, G when installed in accordance with interconnection diagram No. 541-000-012 and with the proper energy limiting barriers.
- Factory Mutual Research Approved as nonincendive for Class I, Division 2, Groups A, B, C, D, and suitable for Class II and III, Division 2, Group G. Barriers are not required for nonincendive rating.
- Canadian Standards Association certified as intrinsically safe when connected through certified diode safety barriers in accordance with Bellofram Installation Instruction 541-000-012.
Explosion proof, intrinsically safe, and non-incendive ratings are not affected by recalibrating for split range or reverse acting applications. The Bellofram T-1000 Transducers were tested and found to comply with Electromagnetic compatibility Directive effective January 1, 1996. The relevant EMC specifications tested were the following: EN 50081-1 (1992) and EN 50082-1 (1992). A Technical Construction File, Serial #107 was written and Certificate of Conformity issued by a Competent Body. |
|
Options: |
Option |
Part Number/Last 3 digits |
Explosion Proof Mounting Kit |
971-079-000 |
Explosion Proof Panel Mounting Kit |
971-078-000 |
DIN Rail Kit |
010-115-000 |
Hirschman Connector Kit (3-prong) |
971-126-000 |
Filter Kit, Coalescing, 0.1 micron |
010-140-000 |
Filter Element Kit (for coalescing filter, package of 10) |
010-141-000 |
Output Gauges–Option “8” |
last 3 digits become - 008 |
Dielectric Strength Testing Option “12” |
last 3 digits become - 012 |
NEMA 4X Type Enclosure Option: Option “4” |
last 3 digits become - 004** |
** NEMA 4 type enclosure option available on all input/output ranges. This option is separate from explosion proof, NEMA 4 units. |
|
|
|
| |
|
|
|
|