Digital Type
|
Model No
|
DED-M10 / M05(Alarm)
|
DER-M10 / M05(Trip)
|
Type approval No
|
07-4 / 07-5
|
07-9 / 07-3
|
Installation
|
10c Flush mounted |
Auxiliary voltage
|
AC 110/220V |
Frequency
|
50 / 60 Hz |
Nominal operating current(A)
|
0.2-0 5-1.0 |
Current
|
Operating
|
53%~75% of nominal operating current 1sec 이내 |
Non operating
|
52% of nominal operating current 30sec 이내 |
Aux Power supply voltage
|
80%~120% of Rated Voltage |
Reset
|
Manual / Auto (multi type) |
Warning circuit voltage
|
Less than AC 600V |
LED indicator |
Leakage circuit indicator : Digital LED |
Detector indicator: LED (Red color) |
Power indicator: LED(Green color) |
ZCT penetration indicator: LED(Yellow color) |
Continue / Auto alarm : LED(Yellow color) |
Buzzer alarm: LED(Yellow color) |
Power consumption
|
Non operating
|
3.5VA / 3.0AV
|
4.5VA /4 AV
|
Operating
|
6.0VA / 5.5AV
|
7VA / 6.5AV
|
ZCT(Input)
|
200㎃ / 100㎷ |
Ambient temperature
|
-10℃ ~ +50℃ |
Sound level
|
Buzzer (more than 75 dB) |
Insulation resistance
|
Primary - Case, Secondary - Case
Primary - Secomdary ▶ more than 100MΩ (DC 500V MEGGER) |
Dielectric strength
|
Primary - Case : 1500V , Secondary - Case : 500V,
Primary - Secomdary : 1500V ▶ AC 60Hz. 1miniute |
Impulse wave withstand voltage
|
Between - terminals,
Power terminals - case ▶ Peak value 6.0Kv 1.2/50㎲ |
Vibration strength
|
On duty : Full wave width 1mm. 1000rpm. 10min.
Not on duty : Full wave width 4mm 1000rpm 60min |
Mechanical shock resistance
|
On duty : natural drop 15times
Not on duty : Accelebration of 50g Max force in any direction for 5 times |
Contect capacity
|
AC 125V 0.5A, DC 30V 2A
|
AC 125V 3A, DC 30V 5A
|
Rate of fuse
|
0.1A
|
0.2A
|
Weight
|
1.9 / 1.7Kg
|
2.0 / 1.8Kg
|
Case
|
ABS Resin/Black N1.5(Non-flamable) |